{"dataType": "CVE_RECORD", "containers": {"cna": {"metrics": [{"format": "CVSS", "cvssV2_0": {"version": "2.0", "baseScore": 6.1, "accessVector": "ADJACENT_NETWORK", "vectorString": "AV:A/AC:L/Au:N/C:N/I:N/A:C", "authentication": "NONE", "integrityImpact": "NONE", "accessComplexity": "LOW", "availabilityImpact": "COMPLETE", "confidentialityImpact": "NONE"}}], "affected": [{"cpes": ["cpe:2.3:a:emerson:deltav_se3006_sd_plus_controller:*:*:*:*:*:*:*:*"], "vendor": "emerson", "product": "deltav_se3006_sd_plus_controller", "versions": [{"status": "affected", "version": "0", "versionType": "custom", "lessThanOrEqual": "11.3.1"}], "defaultStatus": "unaffected"}, {"cpes": ["cpe:2.3:a:emerson:deltav_ve3005_controller_md:*:*:*:*:*:*:*:*"], "vendor": "emerson", "product": "deltav_ve3005_controller_md", "versions": [{"status": "affected", "version": "0", "versionType": "custom", "lessThanOrEqual": "10.3.1"}, {"status": "affected", "version": "0", "versionType": "custom", "lessThanOrEqual": "11.3.1"}], "defaultStatus": "unaffected"}, {"cpes": ["cpe:2.3:a:emerson:deltav_ve3006_controller_md_plus:*:*:*:*:*:*:*:*"], "vendor": "emerson", "product": "deltav_ve3006_controller_md_plus", "versions": [{"status": "affected", "version": "0", "versionType": "custom", "lessThanOrEqual": "10.3.1"}, {"status": "affected", "version": "0", "versionType": "custom", "lessThanOrEqual": "11.3.1"}], "defaultStatus": "unaffected"}], "references": [{"url": "http://ics-cert.us-cert.gov/pdf/ICSA-13-053-01.pdf"}], "descriptions": [{"lang": "en", "value": "The Emerson DeltaV SE3006 through 11.3.1, DeltaV VE3005 through 10.3.1 and 11.x through 11.3.1, and DeltaV VE3006 through 10.3.1 and 11.x through 11.3.1 allow remote attackers to cause a denial of service (device restart) via a crafted packet on (1) TCP port 23, (2) UDP port 161, or (3) TCP port 513."}, {"lang": "es", "value": "El  Emerson DeltaV SE3006 hasta la v11.3.1, DeltaV VE3005 hasta la v10.3.1 y v11.x hasta la v11.3.1, y DeltaV VE3006 hasta la v10.3.1 y 11.x hasta la v11.3.1, permite a atacantes remotos provocar una denegación de servicio (reinicio de dispositivo) a través de un paquete manipulado en los puertos (1)TCP 23, (2)UDP 161 o (3)TCP 513."}], "problemTypes": [{"descriptions": [{"lang": "en", "cweId": "CWE-399", "description": "CWE-399"}]}], "providerMetadata": {"orgId": "00000000-0000-4000-A000-000000000003", "shortName": "nvd", "dateUpdated": "2013-03-11T21:55:02Z", "x_subShortName": "nvd"}}}, "cveMetadata": {"cveId": "CVE-2012-4703", "state": "PUBLISHED", "dateUpdated": "2025-04-11T00:51:21Z", "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6", "datePublished": "2013-03-11T21:55:02Z", "assignerShortName": "icscert"}, "dataVersion": "5.0"}